The following test data were taken on a 15 KVA, 2200/440 V, 60 Hz transformer: Short-circuit test: Open-circuit test: P-620 W P-320 W I=34 A I-IA V-25 V V=440 V a) Calculate the voltage regulation of this transformer when it supplies full load at 0.9 pf lagging. Use the approximate circuit. b) Find the efficiency at the load condition of part (a).
The following test data were taken on a 15 KVA, 2200/440 V, 60 Hz transformer: Short-circuit test: Open-circuit test: P-620 W P-320 W I=34 A I-IA V-25 V V=440 V a) Calculate the voltage regulation of this transformer when it supplies full load at 0.9 pf lagging. Use the approximate circuit. b) Find the efficiency at the load condition of part (a).
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.3P: Consider an ideal transformer with N1=3000andN2=1000 turns. Let winding 1 be connected to a source...
Related questions
Question
thank you
Expert Solution
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
This is a popular solution!
Trending now
This is a popular solution!
Step by step
Solved in 2 steps with 2 images
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning