Refer to the National Electrical Code or the working drawings when necessary. Where applicable, responses should be written in complete sentences. Complete the following table using the following circuits: 1. Eleven 120-volt duplex receptacles for general use. Receptacle loads are considered to be noncontinuous and are not subject to the 80% load limitation as applied for con- tinuous loads.

EBK ELECTRICAL WIRING RESIDENTIAL
19th Edition
ISBN:9781337516549
Author:Simmons
Publisher:Simmons
Chapter28: Overcurrent Protection–fuses And Circuit Breakers
Section: Chapter Questions
Problem 3R
icon
Related questions
Question
100%
8:33
Refer to the National Electrical Code or the working drawings when necessary.
Where applicable, responses should be written in complete sentences.
Complete the following table using the following circuits:
1. Eleven 120-volt duplex receptacles for general use. Receptacle loads are considered
to be noncontinuous and are not subject to the 80% load limitation as applied for con-
tinuous loads,
2. Ten 120-volt fluorescent luminaires, rated at 150 volt-amperes each.
3. Eight 120-volt incandescent luminaires, rated at 200 watts each.
4. One 240-volt exhaust fan, rated at 5000 watts.
5. One 120/240-volt single-phase, 3-wire feeder, 40-kVA continuous load, originating in
a room with an ambient temperature of 100°F (38°C).
Row
Circuit Number
1
3.
1
Calculated Load in Volt-Amperes
Calculated-Load in Amperes
3
Load Type
4
Load Modifier
5
OCPD Selection Amperes
6
OCPD Ampere Rating
7.
Minimum Conductor Ampacity
8.
Minimum Conductor Size Type THHN/THWN
9.
Ambient Temperature
10
Temperature Correction Factor
11 Number of Branch Circuits Required
Number of Current-Carrying Conductors
Raceway Fill Adjustment Factor
Conductor Ampacity Before Correcting/ Adjusting
12
13
14
15
Conductor Ampacity After Correcting/ Adjusting
Factors:
• Circuits 1, 2, 3, and 4 are installed in the same raceway for a distance of 10 ft in an environment where the
maximum ambient temperature will be 86°F (30°C).
• Type THHN/THWN conductors shall be used for all circuits.
• Minimum conductor size 12 AWG.
Row 1:
Calculated load in volt-amperes from problem statements.
Row 2: Calculated load in amperes divided by voltage factor.
Row 3:
Load type: C = continuous; N = noncontinuous; M = motor; R = receptacle.
Transcribed Image Text:8:33 Refer to the National Electrical Code or the working drawings when necessary. Where applicable, responses should be written in complete sentences. Complete the following table using the following circuits: 1. Eleven 120-volt duplex receptacles for general use. Receptacle loads are considered to be noncontinuous and are not subject to the 80% load limitation as applied for con- tinuous loads, 2. Ten 120-volt fluorescent luminaires, rated at 150 volt-amperes each. 3. Eight 120-volt incandescent luminaires, rated at 200 watts each. 4. One 240-volt exhaust fan, rated at 5000 watts. 5. One 120/240-volt single-phase, 3-wire feeder, 40-kVA continuous load, originating in a room with an ambient temperature of 100°F (38°C). Row Circuit Number 1 3. 1 Calculated Load in Volt-Amperes Calculated-Load in Amperes 3 Load Type 4 Load Modifier 5 OCPD Selection Amperes 6 OCPD Ampere Rating 7. Minimum Conductor Ampacity 8. Minimum Conductor Size Type THHN/THWN 9. Ambient Temperature 10 Temperature Correction Factor 11 Number of Branch Circuits Required Number of Current-Carrying Conductors Raceway Fill Adjustment Factor Conductor Ampacity Before Correcting/ Adjusting 12 13 14 15 Conductor Ampacity After Correcting/ Adjusting Factors: • Circuits 1, 2, 3, and 4 are installed in the same raceway for a distance of 10 ft in an environment where the maximum ambient temperature will be 86°F (30°C). • Type THHN/THWN conductors shall be used for all circuits. • Minimum conductor size 12 AWG. Row 1: Calculated load in volt-amperes from problem statements. Row 2: Calculated load in amperes divided by voltage factor. Row 3: Load type: C = continuous; N = noncontinuous; M = motor; R = receptacle.
8:31
1 Search
ul : O
88
CHAPTER 4 Branch Circuits
Row 4: Load modifier, 1.25 for C and M load types, 1.0 for R and N load types.
Row 5: Calculated load amperes (Row 2) multiplied by load modifier (Row 4).
Row 6: OCPD rating equal to or next higher standard ampere rating than OCPD selection amperes
(Row 5).
Row 7: Ampacity of conductor equal to or greater than calculated load amperes (Row 2).
Row 8: Conductor size with ampacity equal to or greater than calculated load amperes (Row 2). Select
from Table 310.16 using the appropriate 60°C for circuits rated 100 amperes or less, and the
75°C column for loads over 100 amperes.
Row 9: From problem statements.
Row 10: From NEC Table 310.15(B)(1).
Row 11: From load calculation.
Row 12: From problem statements.
Row 13: From NEC Table 310.15(C)(1).
Row 14: From NEC 310.16 for conductor type specified in problem statement: (THHN/THWN).
Row 15: Value from Row 13 multiplied by correction and/or adjustment factors. This value must be
equal to or greater than the minimum conductor ampacity value in Row 7.
Transcribed Image Text:8:31 1 Search ul : O 88 CHAPTER 4 Branch Circuits Row 4: Load modifier, 1.25 for C and M load types, 1.0 for R and N load types. Row 5: Calculated load amperes (Row 2) multiplied by load modifier (Row 4). Row 6: OCPD rating equal to or next higher standard ampere rating than OCPD selection amperes (Row 5). Row 7: Ampacity of conductor equal to or greater than calculated load amperes (Row 2). Row 8: Conductor size with ampacity equal to or greater than calculated load amperes (Row 2). Select from Table 310.16 using the appropriate 60°C for circuits rated 100 amperes or less, and the 75°C column for loads over 100 amperes. Row 9: From problem statements. Row 10: From NEC Table 310.15(B)(1). Row 11: From load calculation. Row 12: From problem statements. Row 13: From NEC Table 310.15(C)(1). Row 14: From NEC 310.16 for conductor type specified in problem statement: (THHN/THWN). Row 15: Value from Row 13 multiplied by correction and/or adjustment factors. This value must be equal to or greater than the minimum conductor ampacity value in Row 7.
Expert Solution
Step 1

We are authorized to answer one question at a time, since you have not mentioned question you are looking for, so we are answering the first. Please repost your question separately for the remaining questions.

 

1.Eleven 120-volt duplex receptacles for general use. Receptacle loads are considered to be
noncontinuous and are not subject to the 80% load limitation as applied for continuous loads.

trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 6 steps

Blurred answer
Knowledge Booster
Electric heating unit
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
EBK ELECTRICAL WIRING RESIDENTIAL
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:
9781337516549
Author:
Simmons
Publisher:
CENGAGE LEARNING - CONSIGNMENT