Q2. A small industrial user was fed from a 500 kVA, 11 kV/433 V transformer with a leakage impedance of 4.75% and negligible resistance. He had a 400 kVA 6-pulse rectifier load and site measurements showed excessive levels of harmonic distortion. The user had a 95 kVA power factor correction capacitor bank and the harmonic measurements were carried out with and without this unit, at full load. A significant increase in distortion levels was detected with the PF correction capacitor bank in the circuit. Transformer and capacitor values indicated resonance at about 500 Hz. The difference between measured levels of harmonics with and without the PFC unit was greatest at the 11" harmonic. Calculate the resonant frequency and the THD with and without the power factor correction unit.

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
Q2. A small industrial user was fed from a 500 kVA, 11 kV/433 V transformer with a leakage impedance
of 4.75% and negligible resistance. He had a 400 kVA 6-pulse rectifier load and site measurements showed
excessive levels of harmonic distortion. The user had a 95 kVA power factor correction capacitor bank and
the harmonic measurements were carried out with and without this unit, at full load.
A significant increase in distortion levels was detected with the PF correction capacitor bank in the circuit.
Transformer and capacitor values indicated resonance at about 500 Hz. The difference between measured
levels of harmonics with and without the PFC unit was greatest at the 11" harmonic.
Calculate the resonant frequency and the THD with and without the power factor correction unit.
Transcribed Image Text:Q2. A small industrial user was fed from a 500 kVA, 11 kV/433 V transformer with a leakage impedance of 4.75% and negligible resistance. He had a 400 kVA 6-pulse rectifier load and site measurements showed excessive levels of harmonic distortion. The user had a 95 kVA power factor correction capacitor bank and the harmonic measurements were carried out with and without this unit, at full load. A significant increase in distortion levels was detected with the PF correction capacitor bank in the circuit. Transformer and capacitor values indicated resonance at about 500 Hz. The difference between measured levels of harmonics with and without the PFC unit was greatest at the 11" harmonic. Calculate the resonant frequency and the THD with and without the power factor correction unit.
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,