An opposed louvre type damper is used to regulate air flow to a furnace in order to control the furnace temperature. The minimum and maximum louvre openings are 10 degrees and 90 degrees respectively. An angular actuator of the electronic type operates the louvres and it is controlled with 0-10V (0 degrees to 90 degrees opening). It gives a feedback of 0-10V relative to the actual position. The PLC analogue input and output cards are 4-20mA loop, but transmitters are used to linearly scale 0-10V to 4-20mA.   a)      Calculate the mA's that the PLC will read as feedback when the louvres are at 10 degrees. Instead of using louvres to regulate air flow with a fan motor running at constant speed, we can use a VSD (Variable speed drive) to regulate the air-flow by varying the motor speed thereby conserving energy. b)  If the VSD is controlled by a 4-20mA loop regulating the speed of the motor, calculate the mA required to set the motor to run at 50% speed?

Introduction to Chemical Engineering Thermodynamics
8th Edition
ISBN:9781259696527
Author:J.M. Smith Termodinamica en ingenieria quimica, Hendrick C Van Ness, Michael Abbott, Mark Swihart
Publisher:J.M. Smith Termodinamica en ingenieria quimica, Hendrick C Van Ness, Michael Abbott, Mark Swihart
Chapter1: Introduction
Section: Chapter Questions
Problem 1.1P
icon
Related questions
Question

An opposed louvre type damper is used to regulate air flow to a furnace in order to control the furnace temperature. The minimum and maximum louvre openings are 10 degrees and 90 degrees respectively. An angular actuator of the electronic type operates the louvres and it is controlled with 0-10V (0 degrees to 90 degrees opening). It gives a feedback of 0-10V relative to the actual position. The PLC analogue input and output cards are 4-20mA loop, but transmitters are used to linearly scale 0-10V to 4-20mA.

 

a)      Calculate the mA's that the PLC will read as feedback when the louvres are at 10 degrees.

Instead of using louvres to regulate air flow with a fan motor running at constant speed, we can use a VSD (Variable speed drive) to regulate the air-flow by varying the motor speed thereby conserving energy.

b)  If the VSD is controlled by a 4-20mA loop regulating the speed of the motor, calculate the mA required to set the motor to run at 50% speed?

Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 1 steps with 4 images

Blurred answer
Recommended textbooks for you
Introduction to Chemical Engineering Thermodynami…
Introduction to Chemical Engineering Thermodynami…
Chemical Engineering
ISBN:
9781259696527
Author:
J.M. Smith Termodinamica en ingenieria quimica, Hendrick C Van Ness, Michael Abbott, Mark Swihart
Publisher:
McGraw-Hill Education
Elementary Principles of Chemical Processes, Bind…
Elementary Principles of Chemical Processes, Bind…
Chemical Engineering
ISBN:
9781118431221
Author:
Richard M. Felder, Ronald W. Rousseau, Lisa G. Bullard
Publisher:
WILEY
Elements of Chemical Reaction Engineering (5th Ed…
Elements of Chemical Reaction Engineering (5th Ed…
Chemical Engineering
ISBN:
9780133887518
Author:
H. Scott Fogler
Publisher:
Prentice Hall
Process Dynamics and Control, 4e
Process Dynamics and Control, 4e
Chemical Engineering
ISBN:
9781119285915
Author:
Seborg
Publisher:
WILEY
Industrial Plastics: Theory and Applications
Industrial Plastics: Theory and Applications
Chemical Engineering
ISBN:
9781285061238
Author:
Lokensgard, Erik
Publisher:
Delmar Cengage Learning
Unit Operations of Chemical Engineering
Unit Operations of Chemical Engineering
Chemical Engineering
ISBN:
9780072848236
Author:
Warren McCabe, Julian C. Smith, Peter Harriott
Publisher:
McGraw-Hill Companies, The