A heat pump is installed in a building to heat the space to a constant 22 ⁰C when the outdoor temperature is 15 ⁰C. The heating requirement at these conditions is 30 kW. The system uses R-410a as a refrigerant and operates according to an ideal vapor compression cycle as shown in the figures below. The saturation temperature of the refrigerant in the indoor coil is typically 20 ⁰C higher than the desired space temperature, and the saturation temperature of the refrigerant in the outdoor unit is typically 20 ⁰C lower than the outdoor temperature. (one of those coils is the condenser, the other is the evaporator) Determine the states at points 1 through 4.
A heat pump is installed in a building to heat the space to a constant 22 ⁰C when the outdoor temperature is 15 ⁰C. The heating requirement at these conditions is 30 kW. The system uses R-410a as a refrigerant and operates according to an ideal vapor compression cycle as shown in the figures below. The saturation temperature of the refrigerant in the indoor coil is typically 20 ⁰C higher than the desired space temperature, and the saturation temperature of the refrigerant in the outdoor unit is typically 20 ⁰C lower than the outdoor temperature. (one of those coils is the condenser, the other is the evaporator) Determine the states at points 1 through 4.
Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter45: Domestic Refrigerators And Freezers
Section: Chapter Questions
Problem 2RQ: The operating condition for the single compressor in a household refrigerator is the lowest box...
Related questions
Question
A heat pump is installed in a building to heat the space to a constant 22 ⁰C when the outdoor temperature is 15 ⁰C. The heating requirement at these conditions is 30 kW. The system uses R-410a as a refrigerant and operates according to an ideal vapor compression cycle as shown in the figures below.
The saturation temperature of the refrigerant in the indoor coil is typically 20 ⁰C higher than the desired space temperature, and the saturation temperature of the refrigerant in the outdoor unit is typically 20 ⁰C lower than the outdoor temperature. (one of those coils is the condenser, the other is the evaporator)
- Determine the states at points 1 through 4.
Expert Solution
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
This is a popular solution!
Trending now
This is a popular solution!
Step by step
Solved in 3 steps with 5 images
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning